Red Lion GEMINI 2 User Manual

Page 31

Advertising
background image

The Gemini is intended to be mounted into an enclosed panel with a gasket

to provide a water-tight seal. The unit meets NEMA 4/IP65 requirements for

indoor use when properly installed. Two mounting clips and screws are

provided for easy installation. Consideration should be given to the thickness

of the panel. Too thin of a panel may distort and not provide a water-tight seal.

(Recommended minimum panel thickness is 1/8".)

After the panel cut-out has been completed and deburred, remove the

backing from the adhesive side of the gasket, and carefully stick the gasket to

the panel. DO NOT APPLY THE ADHESIVE SIDE OF THE GASKET TO

THE COUNTER BEZEL. Insert the unit into the panel. As depicted in the

drawing, install the screws into the narrow end of the mounting clips. Thread

the screws into the clips until the pointed end just protrudes through the other

side. Install each of the two

mounting clips by inserting the wide

lip of the clips into the wide end of

the holes located on either side of the

case. Tighten the screws evenly to

apply uniform compression, thus

providing a water-tight seal.

CAUTION: Only minimum

pressure is required to seal panel. Do

NOT overtighten mounting screws.

–29–

APPENDIX “A” - INSTALLATION & INPUT CONFIGURATION SWITCH SET-UP

Before installing the Gemini into the panel, the user should first become

familiar with the unit. It may also be desirable to program the unit for the

application at hand (Refer to the “Programming and Applications” sections).

Once the unit is programmed, the settings will be saved in memory. The Program

Disable “PGM. DIS.” terminal should be connected to “COMM.” to prevent

accidental or unauthorized programming changes.

Installation Environment

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near

devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product. Do

NOT use solvents. Continuous exposure to direct sunlight may accelerate the

aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

PANEL MOUNTING (Note, See Appendix “B” for Dimensions)

Advertising