GEMINI 1000 SENSOR INPUT CONNECTIONS & INPUT CONFIGURATION SWITCH SET-UP

The accompanying diagram shows the details of the count Input A and

magnetic pickup circuit. The schematic circuit for Input B is almost identical to

that of Input A, with the exception that Input B does not have the Magnetic

Pickup circuitry paralleled with it. The four switches used to set up Input A and

the Magnetic Pickup are designated S1, S2, S3, and S4. To set up Input B; use

switches S5, S6, and S7. The functions of these switches are as follows:

S1 - MAG: Enables the Magnetic Pickup terminal to be used.

LOGIC: Disables the Magnetic Pickup Input.

Note: SWITCH S2 MUST BE IN THE “SNK” POSITION FOR

MAGNETIC PICKUP INPUT.

S2 - SNK: Provides a 7.8 K pull-up resistor for sensors with sinking

outputs.

SRC: Provides a 3.9 K pull-down resistor for sensors with sourcing

outputs.

S3 - HI FRQ: Removes damping capacitor and allows operation up to 10

KHz. Minimum count ON/OFF times - 50 usec.

LO FRQ: Connects damping capacitor for switch contact debounce.

Limits count speed to 100 cps max. Min. count pulse ON/OFF time - 5

msec.

S4 - HI BIAS: Sets input trigger levels at mid-range to accept outputs from

2-wire proximity sensors, resistive photo-cells, and logic pulses with

full 0 to +12 V swings. (V

IL

= 5.5 V, V

IH

= 7.5 V)

LO BIAS: Sets input trigger levels to the low range to accept logic

pulses with 0 to 5 V swings. (V

IL

= 1.5 V, V

IH

= 3.75 V)

S5 - Same as S2, for Input B - does not affect Magnetic Pickup Input.

S6 - Same as S3, for Input B.

S7 - Same as S4, for Input B.

S8 - DIS. RST.: Disables front panel reset.

EN. RST.: Enables front panel reset if “Operator Accessible

Functions” mode (Code 66) has Reset enabled.