Red Lion GEMINI 2 User Manual

Page 35

Advertising
background image

Additional EMC Installation Guidelines

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods

must be followed to ensure compatibility in each application. The type of the

electrical noise, source or coupling method into the unit may be different for

various installations. Listed below are some additional EMC guidelines for

successful installation in an industrial environment.
1. The unit should be mounted in a metal enclosure, which is properly connected

to protective earth.

a. If the bezel is exposed to high Electro-Static Discharge (ESD) levels,

above 4 Kv, it should be connected to protective earth. This can be done

by making sure the metal bezel makes proper contact to the panel cut-out

or connecting the bezel screw with a spade terminal and wire to

protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The

connection point for the shield depends somewhat upon the application.

Listed below are the recommended methods of connecting the shield, in order

of their effectiveness.

a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually

when the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and heaters,

etc. The cables should be run in metal conduit that is properly grounded. This

is especially useful in applications where cable runs are long and portable

two-way radios are used in close proximity or if the installation is near a

commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy

components.

5. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal and

Control cables as close to the unit as possible. Loop the cable through the core

several times or use multiple cores on each cable for additional protection.

Install line filters on the power input cable to the unit to suppress power line

interference. Install them near the power entry point of the enclosure. The

following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)

TDK # ZCAT3035-1330A

Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)

Schaffner # FN670-1.8/07

Corcom #1VR3

Note: Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

7. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.

Snubbers:

RLC #SNUB0000

WIRING CONNECTIONS

After the unit has been mechanically mounted, it is ready to be wired. All

conductors should meet voltage and current ratings for each terminal. Also

cabling should conform to appropriate standards of good installation, local codes

and regulations. It is recommended that power supplied to the unit (AC or DC) be

protected by a fuse or circuit breaker.

All wiring connections are made on removable plug-in terminal blocks. There is

a separate terminal block for the count inputs, bottom board, optional relay board,

and optional 20 mA current loop. When wiring the unit, remove the terminal block

and refer to the “Block Diagram” to identify the terminal block position number

with the proper function. Simply strip the wire, leaving approximately 1/4" bare

wire exposed (standard wires should be tinned with solder). Insert the wire into the

terminal and tighten down the screw until wire is clamped in tightly. Each terminal

can accept up to two 18-gage wires. After the terminal block is wired, install in

proper location on board. Wire each terminal block in this manner.

–33–

Advertising
This manual is related to the following products: