APPENDIX “D” - GEMINI FUNCTION COMMAND CODE SUMMARY

–45–

CODE

MODE

DESCRIPTION

COMMENTS

41

UNIT PERSONALITY

1

Counter

2

Rate

Automatically selects [51 1], [52 6] & [54 6] if [54 1,2] or[52 1,2] was

programmed.

43

INPUTS A & B RESPONSE MODES (counter only)

1

Count with Inhibit

Input A = Count, Input B = Inhibit

2

Count with Up/Down Control

Input A = Count, Input B = Up/Down

3

Input Anti-Coincidence Add/Subtract

Input A = Add, Input B = Subtract

4

Input Anti-Coincidence Add

5

Quadrature

6

Quadrature x4

44

NUMBER OF COUNT EDGES

Cannot be programmed in Quad x4.

1

1

Count on falling edge of count input.

2

2

Count on both edges of count input.

45

SCALE MULTIPLIER

1

1

2

0.1

3

0.01

4

0.001

46

DECIMAL POINT & LEADING ZERO BLANKING

-

(+) Leading Zero Blanking Enabled

-

(-) Leading Zero Blanking Disabled

*

+/-1

No Decimal Point

+/-2

Decimal Point Right of Digit 2

+/-3

Decimal Point Right of Digit 3

+/-4

Decimal Point Right of Digit 4

+/-5

Decimal Point Right of Digit 5

+/-6

Decimal Point Right of Digit 6

*Polarity sign is displayed in front of the identifier, a (-) sign is displayed, a (+) sign is not.