Red Lion GEMINI 2 User Manual

Page 19

Advertising
background image

the case with all standard rate indicators. In order to ensure this type of operation,

it is important that the reset Disable/Enable switch be disabled to preclude any

unwanted re-start of the sample time cycle.

Certain special application requirements may exist for the sample time cycle to

commence at a specific time. In these applications, the remote reset terminal or the

front panel reset button (if the Disable/Enable switch is set to the enable position),

maybeusedtoactivatethefollowingtworesetmodes,thusstartingthesampletime.
[51 1] MANUAL RESET TO ZERO (RTZ) - Manual reset to zero is

accomplished by pulling remote reset to ground or by pressing the front panel

reset button. In this mode the sample time is initiated immediately upon

release of the reset button.

[51 -1] MANUAL RESET TO ZERO (RTZ) - Same as [51 1] except that the

sample time is initiated immediately upon pressing the reset button.

CODE 52 - OUTPUT 1 TERMINATION MODES

The Gemini has two standard Output 1 Termination Modes when operating as

a rate indicator. They are: Terminate After Time Delay and Boundary.

A reverse phase option is available on the Gemini. This refers to

complementing the logic state of the output. For normal phase operation the reset

condition of the output is output off. For reverse phase operation the reset

condition of the output is output on. (Note: The state of the relay, if used, is also

reversed.) A “-” sign in front of the mode identifier will provide for reverse

phase operation. The absence of a “-” sign will give normal phase operation.
[52 5] TERMINATE AFTER OUTPUT 1 TIME DELAY - In this mode, output 1

activates at the end of each sample time in which the rate is lower than Preset 1.

Once the output has been activated, it will deactivate after the predetermined

length of output 1 time delay has expired. If the output 1 time delay is longer

than the sample time, the output time delay will continually be restarted without

timing out until the rate exceeds the Preset 1 value. Manual reset, by either the

front panel button or the reset terminal, will override the output time delay and

reset the output. The output is set for normal phase operation.

[52 6] BOUNDARY MODE - When in the boundary mode, the preset 1 value

serves as the boundary point. When the rate value is more negative than the

preset, the output is not activated. When the rate value is more positive than or

equal to the preset, the output activates. If the rate value were to drop below

preset, the output would again deactivate. For negative preset points (Negative

Scale Factor), the output is not activated when the rate value is more positive

than the preset value. When the rate value is more negative than or equal to the

preset, the output is activated. If the rate value becomes more positive than the

preset, the output again deactivates. The output is set for normal phase.

In addition, when functioning as a rate indicator, the Gemini also has two special

use function modes, Terminate at Manual Reset and Terminate at Manual

Reset End. These modes are infrequently used. However, they may be useful

when a requirement exists to latch and manually release the output.

[52 3] TERMINATE AT MANUAL RESET - In this mode, Output 1 activates

when the rate exceeds the Preset 1 value. Once activated, the output does not

deactivate until the moment a reset occurs. The reset can be from the front

panel button or from the remote reset terminal, at the rear of the unit. The

output is set for normal phase operation.

[52 4] TERMINATE AT MANUAL RESET END - This mode is like the

preceding output mode, except the output deactivates when the reset ends. The

output is set for normal phase operation.

[52 -3]

[52 -4]

These modes are the same as above with the exception

[52 -5]

that the output is set for reverse phase operation.

[52 -6]

CODE 53 - OUTPUT 1 TIME DELAY

The Gemini has the capability of varying the output time delay from 0.01 second

to 599.99 seconds. When the code is entered, instead of a single mode identifier

digit being displayed, six digits will be shown. Refer to the “Programming Preset,

Scale Factor, and Output Time Delay” section for more details about entering.

Output time delay will be terminated if the unit is manually reset.
Note: A time delay value of zero cannot be programmed into the Gemini. If a

value of 0 is entered into the display and the “E” key is pressed, the unit will

not enter the 0, but will revert back to displaying the previous time delay.