CURRENT LOOP INSTALLATION (Cont’d)

SERIAL DIP SWITCH SET-UP

The Serial DIP switches are accessible through the side of the Gemini 2000. A

list of the DIP switch positions and their functions are shown in Figure 5.
BR0 & BR1, BAUD RATE - Set-up is shown in Figure 5, below. When

changing the Baud Rate, the unit should be powered-down and then powered

back up again. The unit will only recognize a baud rate change upon power-up,

after activating the “Print Request” terminal or after a few characters have

been sent at the new baud rate (If the two previous conditions have not

occurred, the Gemini will see the characters as erroneous and it will check the

baud rate and set itself to operate at the new rate).

PR.ID - PRINT ID. - When this switch is in the up position, the Gemini 2000

will print the unit address, data value ID and the data value when a

transmission is requested. The unit will also insert a 400 msec delay between

transmissions when the “P” command or Print Request terminal is used. This

switch position is generally used when the unit is connected with a printer.

When the switch is in the down position, the Gemini 2000 will transmit only the

data value, without the unit address and data ID. The 400 msec delay, described

above, will not be inserted. This switch position usage is intended for applications

where the Gemini is communicating with a computer. In these circumstances

printing the address and value ID and inserting a 400 msec print delay is usually

unnecessary and needlessly slows down communication throughput.

PC0 & PC1, PRINT OPTIONS - Used to control which values are transmitted

when the Print Request terminal is activated or when the Transmit per Print

Options command “P” is sent to the Gemini 2000.

TRST, TRANSMIT CNT & RESET - Used in conjunction with Print Options.

When this switch is in the down position, the unit will transmit and reset the count

whenthe“PRINT.REQ.”terminalisactivatedorthe(P)commandisreceived.

AD0, AD1, AD2 & AD3, UNIT ADDRESS - These switches are used to give

each unit a separate address when more than one unit is connected in the Loop.

See Figure 5, for Switch Set-up.

–26–

FIG. 5: DIP SWITCH SET-UP

When connecting a printer or any

device in which the Gemini 2000’s Serial

Inputs (SI+, SI-) are not used, they must

still be connected to a 20 mA source and

be in the Mark condition (Current on) in

order for the Gemini 2000 to respond to a

Print Request.