SELECT AC POWER (115/230 VAC)

The AC power to the unit must be selected for either 115 VAC or 230 VAC.

The selector switch is located through an access slot on the side of the case (See

the Installation Figure on the previous page, or the label on the case). The unit is

shipped from the factory with the switch in the 230 VAC position.

Caution: Damage to the unit may occur if the AC selector switch is set

incorrectly.

EMC Compliance Installation

This unit complies with the Electromagnetic Compatibility (EMC) standards

listed in the specifications. Compliance to the EMC standards was demonstrated

by means of a test set-up using the following installation methods:

1. Unit mounted in a metal panel connected to earth ground (protective earth).

2. Shielded (screened) cables for Signal and Control inputs with shield drain wire

connected to earth ground at the mounting panel only.

Multi-conductor Cable

Function Used For

Belden #8771 - 3 conductor, #22 AWG

with foil shield and drain wire

Input A, Input B, PGM DIS,

and REM RST

Alpha #2404 - 4 conductor, #22 AWG

with foil shield and drain wire

20 mA serial option

Alpha #1173C - 3 conductor, #22 AWG

non-shielded

Relay Outputs and

Solid State Outputs

3. Metal bezel of unit connected to mounting panel with 9 inch (23 cm) ground

lead from rear bezel screw. Test: Immunity to ESD per EN 61000-4-2.

4. EMI filter (Shaffner FN610) placed on the DC mains cable for EMI

frequencies above 40 MHz when using optional power supply. Test: RF

Conducted Immunity EN 61000-4-6

Shield Termination

EMC compliance installation testing had the drain wire for the shielded cable

terminated as shown. The drain wire was less than 0.5" (12.7 mm) long.

–32–