Auxiliary-piping checklist, Uxiliary-piping checklist – Goulds Pumps 3180-86 - IOM User Manual

Page 43

Advertising
background image

Check

Explanation/comment

Checked

See Example: Discharge piping equipment for

illustrations.

Check that a check valve is installed in

the discharge line, between the

isolation valve and the pump discharge

outlet.

The location between the isolation valve and the

pump allows inspection of the check valve.
The check valve prevents damage to the pump and

seal due to the back flow through the pump, when

the drive unit is shut off. It is also used to restrain

the liquid flow.
See Example: Discharge piping equipment for

illustrations.

If increasers are used, check that they

are installed between the pump and the

check valve.

See Example: Discharge piping equipment for

illustrations.

If quick-closing valves are installed in

the system, check that cushioning

devices are used.

This protects the pump from surges and water

hammer.

Example: Discharge piping equipment

Correct

Incorrect

1

2

3

4

1.

Bypass line

2.

Shut-off valve

3.

Check valve

4.

Discharge isolation valve

2

1

1.

Check valve (incorrect position)

2.

The isolation valve should not be positioned
between the check valve and the pump.

Auxiliary-piping checklist

Precautions

WARNING:

• Cooling systems such as those for bearing lubrication and mechanical-seal systems must be operating

properly to prevent excess heat generation, sparks, and premature failure.

• Sealing systems that are not self-purging or self-venting, such as plan 23, require manual venting prior

to operation. Failure to do so will result in excess heat generation and seal failure.

NOTICE:
The mechanical seal must have an appropriate seal-flush system. Otherwise, excess heat generation and
seal failure can occur.

Installation

Models 3180, 3181, 3185, and 3186 Installation, Operation, and Maintenance Manual

41

Advertising