2 fault functions of the sec-st, Fault functions of the sec−st, 2 fault functions of the sec−st – Festo Контроллер двигателя SEC-ST User Manual

Page 62

Advertising
background image

5. Diagnosis and error treatment

5−4

Festo SEC−ST−48−6−P01−EN en 0606c

5.2

Fault functions of the SEC−ST

Fault

Cause

Possibilities

Power LED does not light up

No supply voltage

Ĉ Check supply cable
Ĉ Check power unit

Fault LED lights up red

Short circuit at motor output

Ĉ Check motor
Ĉ Check motor cable

Final stage overheated

Ĉ Winding resistor of motor too

small

Ĉ Motor defective, check
Ĉ Check fitting of controller

Motor does not move, power
LED lights up blue red fault LED

Dip switch 8 off

Ĉ Dip switch 8 on

LED lights up blue, red fault LED
is out

Motor cable defective

Ĉ Check motor cable

Brake not activated

Ĉ Open brake by applying

24ĂV DC

Motor loses steps

Frequency too high

Ĉ Check characteristic curve of

motor, check which torque
can be given

Motor cannot give torque
required

Ĉ Reduce frequency

(controller)

Fig. 5/1:

Advertising