Output (outputs) – APG MND user manual User Manual

Page 12

Advertising
background image

MND

Rev. A1, 5/14

12

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• OUTPUT (Outputs)

The MND is off ered with op onal outputs, such as solid-state relays, or 4-20 mA
or 0-5 Vdc analog signals. Not all output menu op ons are applicable to all MND
confi gura ons.

NOTE: when displaying the readings from mul ple sensors, the Sensor Address se ng
determines which sensor is controlling the output(s) of the MND.

AL SET

(Analog Low Set-point): sets the reading associated with the low analog value

(either 4mA or 0V). Used for analog output or analog input.

AH SET

(Analog High Set-point): sets the reading associated with the high analog value

(either 20mA or 5V). Used for analog output or analog input.

AL CAL

(Analog Low Calibra on): adjusts the low end of the analog output (either 4mA

or 0V). Increasing/decreasing the value will cause an increase/decrease at the low end
of the analog output.

AH CAL

(Analog High Calibra on): adjusts the high end of the analog output (i.e. either

20mA or 5V). Increasing/decreasing the value will cause an increase/decrease at the
high end of the analog output.

T1TYPE

&

T2TYPE

(Trip 1&2 Type): determines the basic func onal logic of the solid-

state relay outputs as described in the Trip Type descrip ons on pages 14-16.

NOTE: the MND’s solid-state relays are rated for a maximum switched load of 120 mA.

T1REAd

&

T2REAd

(Trip 1&2 Reading): defi nes the display reading that corresponds

to a change in the state of the associated relay output, as determined by the Trip Type
selected.

T1 WIN

&

T2 WIN

(Trip 1&2 Window): defi nes the secondary value (beginning from

the Trip Reading) for Exclusive, Inclusive, and Hysteresis Near & Far Trip Types (refer to
descrip ons below). For example: if the Trip Reading is set to 250, and the secondary
trip value is desired at a reading of 350, then the Trip Window should be set to 100.
(250 + 100 = 350)

Advertising
This manual is related to the following products: