APG MND user manual User Manual

Page 15

Advertising
background image

Rev. A1, 5/14

MND

15

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

“ON” TIME
(in seconds)

Relay “ON” (closed)

Relay “OFF”(open)

INTERVAL TIME

(in minutes)

Trip Type Descrip ons (con nued)

LOERST

(LOE/RST):

forces the output to follow the state of the corresponding output of an LOE or RST
sensor ac ng as the master device. For example, whenever output T1 of the LOE/RST
ac vates/deac vates, then output T1 of the MND will ac vate/deac vate as well.

TIME R

(Timed Interval):

sets the output to ac vate on a med interval. The Interval-Time (

INTMIN

) sets the

me between ac va ons (in minutes), and the On-Time (

ON SEC

) determines how

long the output remains ac ve at each interval (in seconds).

NOTE: when using the Timed Interval in conjunc on with the Auto-Off feature, the
MND will wake (power on) at each Interval and will remain powered on for the
dura on of the relay On-Time regardless of the Auto-Off se ng.

*

H TEMP

(Heater Temperature):

The LCD heater is controlled using Trip Relay 1. Set the heater “on” temperature
using the Trip 1 Reading (

T1READ

) parameter (in

0

C). The Trip 1 Window (

T1 WIN

)

parameter is used to set the “off ” temperature, defi ned by the number of degrees above
the on temperature.

For Example: to ac vate the heater at -30

0

C and deac vate the heater above -10

0

C

T1TYPE set to H TEMP

T1READ

set to -0030

T1

WIN

set to 00020

*Op onal Feature

Advertising
This manual is related to the following products: