Mp series magnetostric ve – APG MND user manual User Manual

Page 30

Advertising
background image

MND

Rev. A1, 5/14

30

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

MP Series Magnetostric ve

Input Registers (0x04):

Register

Type

Returned Data

30300

U16

Raw Top Float Reading (in mm, unsigned)

30301

U16

Raw Bo om Float Reading (in mm, unsigned)

30302

S16

Temperature Reading (in

0

C, signed)

30303-30304

U32

Calculated Top Float Reading (in selected Units)

30305-30306 U32 Calculated

Bo om Float Reading (in selected Units)

Holding Registers (0x03):

Register

Type

Descrip

on

Value

Range

40400

U16

Device

Address

1

to

255

40401

U16

Units

1

to

3

40402

U16

Applica on Type

0-10

40403

U16

Volume Units

0 to 6

40404

U16

Decimal

Place

0

to

3

40405

U16

Max Distance

0 to 10364 mm

40406

U16

Full Distance

0 to 10364 mm

40407

U16

Empty Distance

0 to 10364 mm

40408

U16

Sensi

vity 0

to

100

40409

U16

Pulses

0

to

20

40410

U16

Blanking

0

to

10364

mm

40411

reserved

40412

U16

Averaging 0

to

100

40413

U16

Filter Window

0 to 10364 mm

40414

U16

Out of Range Samples

0 to 255

40415

U16

Sample Rate

50 to 1000 msec.

40416

U16

Mul

plier 1

to

1999

40417

S16

Off

set

+/-

10364

mm

40418-40420

reserved

40421

S16

RTD Off set (0C)

-100 to 100

40422

U16

Float Window

0 to 1000 mm

40423

U32

Top Float Off

set

+/-

10364

mm

40424

U32

Bo om Float Off

set

+/-

10364

mm

40425

U32

Gain Off

set

0

to

255

40426-40435

reserved

40436-40437 U32

Parameter 1 Data

0 to 100000 mm

40438-40439 U32

Parameter 2 Data

0 to 100000 mm

40440-40441 U32

Parameter 3 Data

0 to 100000 mm

40442-40443 U32

Parameter 4 Data

0 to 100000 mm

40444-40445 U32

Parameter 5 Data

0 to 100000 mm