Communica ons Setup Examples
For APG sensors, the sensor readings are stored in register 303, which is an unsigned
32-bit register.
MND master displaying readings from a single sensor (address 1):
C-Type = Master
Number of Sensors = 1
Sensor Address = 1
Register Number = 303
Func on = 4
Register Type = U32 (unsigned 32-bit)
MND master displaying mul ple sensor readings (addresses 1-6):
C-Type = Master
Number of Sensors = 6
Sensor Address = n/a (sensors addresses must begin at 1)
Register Number = 303
Func on = 4
Register Type = U32 (unsigned 32-bit)
MND in Sniff er mode displaying readings from a single sensor (address 3):
C-Type = Sniff er
Number of Sensors = 1
Sensor Address = 3
Register Number = 303
Func on = 4
Register Type = U32 (unsigned 32-bit)
MND displaying the readings from 2 sensors + an LOE ultrasonic:
C-Type = LOE/RST Sniff er (LRSNIF)
Number of Sensors = 2 (the LOE sensor is assumed and not included in the count)
Sensor Address = n/a (sensors addresses are assumed to begin at 1)
Register Number = 303
Func on = 4
Register Type = U32 (unsigned 32-bit)