APG MND user manual User Manual

Page 18

Advertising
background image

MND

Rev. A1, 5/14

18

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

NUMSEN

(Number of Sensors): sets the number of sensors to be monitored. When

using the MND to display readings from mul ple sensors, the sensor addresses must
begin at 1 and increment sequen ally (see note above).

REGNUM

(Register Number): sets the register number to be displayed. The readings of

APG sensors are stored in register 30303.

NOTE: the register number is entered using only the last 3 digits of the full register
number. For example, register 30303 would be entered as 303, or register 40401
would be entered as 401.

FUNCTN

(Func on): sets the func on code for the register to be displayed; 3 = holding

resister, 4 = input register. Sensor readings are stored in input registers, while sensor
parameter values are stored in holding registers.

REGTYP

(Register Type): sets the bit type of the register to be displayed. Op ons are:

signed, 8 bit, low byte (S8L)

signed, 16 bit (S16)

signed, 8 bit, high byte (S8H)

unsigned, 16 bit (U16)

unsigned, 8 bit, low byte (U8L)

signed, 32 bit (S32)

unsigned, 8 bit, high byte (U8H)

unsigned, 32 bit (U32)

NOTE: the readings of APG’s sensors are stored as an unsigned 32-bit value. Refer
to the sensor’s user manual for a list of register numbers and their corresponding
register types.

SCANRT

(Scan Rate): determines how o en the MND polls the sensor(s) (in seconds)

when opera ng in Master mode.

Advertising
This manual is related to the following products: