• SENLAb (Sensor Labels)

Allows the user to assign a custom label for each sensor being displayed (up to 10
sensors + an LOE/RST master). The sensor label will appear on the lower display line,
which will alternate between the Sensor Label and the selected Unit of measure.

NOTE: Se ng a Mode Access Password

(refer to Access Modes on page 7).

If a label is assigned for Sensor 10, the label becomes the password to access the
Mode se ng. If the label for sensor 10 is set to the default of

10AAAA

, then no

password will be required to access the Mode se ng.

• PCTFUL (Percent Full)

Allows sensor readings to be displayed as a percentage of full based on a user defi ned
100% value.

To enable the Percent Full feature, select

PCTFUL

in the main menu. Select the sensor

number you want to display as a percentage of full, and enter the value associated with
100%. 0% (empty) is assumed to be 0. Se ng the value to 00000 (default) will disable
the Percent Full feature.

NOTE: the label

PCTFUL

will be automa cally be displayed as the units of measure

for all sensors running in Percent Full mode.

NOTE: when controlling one of the MND’s outputs with a sensor setup to display in
Percent Full mode, the se ngs controlling the output need to be entered based on
the underlying readings and not the displayed percentage value.

• *bLIGHT (Back Light)

*Op onal Feature

The Mode op ons include: On, Off , 30 Sec, 1 min, 2 min, 4 min, 8min and 16 min. To
adjust the backlight intensity, select brightness (

bRTNES

) in the menu and use the up/

down arrow bu ons to increase/decrease the brightness.