Input (analog input) – APG MND user manual User Manual
Page 21

Rev. A1, 5/14
MND
21
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
• *INPUT (Analog Input)
*Op onal Feature
Used to adjust how the MND reads the analog input signal.
SAM RT
: determines how o en the MND reads the analog input signal.
AVERGE
: determines how many readings of the analog signal will be averaged together
to become the displayed reading. A higher average se ng will result in smoother
readings but will also cause slower response to rapid changes.
The following is a list of parameters required to read an analog input:
COMM menu:
Set
C-TYPE to AINPUT.
OUTPUT menu:
Set
AL SET to the value associated with a 4mA input signal.
Set
AH SET to the value associated with a 20mA input signal.
*Adjust
AL CAL and AH CAL as necessary.
INPUT menu:
*Adjust
SAM RT as necessary.
*Adjust
AVERAGE as necessary.
*parameters normally do not require adjustment.