Input (analog input) – APG MND user manual User Manual

Page 21

Advertising
background image

Rev. A1, 5/14

MND

21

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• *INPUT (Analog Input)

*Op onal Feature

Used to adjust how the MND reads the analog input signal.

SAM RT

: determines how o en the MND reads the analog input signal.

AVERGE

: determines how many readings of the analog signal will be averaged together

to become the displayed reading. A higher average se ng will result in smoother
readings but will also cause slower response to rapid changes.

The following is a list of parameters required to read an analog input:

COMM menu:
Set

C-TYPE to AINPUT.

OUTPUT menu:
Set

AL SET to the value associated with a 4mA input signal.

Set

AH SET to the value associated with a 20mA input signal.

*Adjust

AL CAL and AH CAL as necessary.

INPUT menu:
*Adjust

SAM RT as necessary.

*Adjust

AVERAGE as necessary.

*parameters normally do not require adjustment.

Advertising