Trip Type Descrip ons

Refer to the chart on the next page for an illustra on of Near, Far, Exclusive, Inclusive
and Hysteresis Near & Far trip types.

NEAR

:

The output will ac vate whenever the reading is less than the Trip Reading se ng (refer
to chart on next page).

EXCLSV

(Exclusive):

The output will ac vate whenever the reading is less than the Trip Reading OR greater
than the Trip Reading + Trip Window (refer to chart on next page).

H NEAR

(Hysteresis Near):

The output will ac vate un l the reading is greater than the Trip Reading + Trip Window,
at which point the output will deac vate and remain in that state un l the reading is less
than the Trip Reading (refer to chart on next page).

FAR

:

The output will ac vate whenever the reading is greater than the Trip Reading (refer to
chart on next page).

INCLSV

(Inclusive):

The output will ac vate whenever the reading is greater than the Trip Reading and less
than the Trip Reading + Trip Window (refer to chart on next page).

H FAR

(Hysteresis Far):

The output will ac vate when the reading increases beyond the Trip Reading + Trip
Window, and will remain ac ve un l the reading falls below the Trip Reading. The
output will remain deac vated un l the reading is once again greater than the Trip
Reading + Trip Window (refer to chart on next page).

ON

:

Holds the output closed whenever the display is powered.

OFF

:

Disables the output.

(con nued on pages 15-16)