Trip Type Descrip ons
Refer to the chart on the next page for an illustra on of Near, Far, Exclusive, Inclusive
and Hysteresis Near & Far trip types.
NEAR
:
The output will ac vate whenever the reading is less than the Trip Reading se ng (refer
to chart on next page).
EXCLSV
(Exclusive):
The output will ac vate whenever the reading is less than the Trip Reading OR greater
than the Trip Reading + Trip Window (refer to chart on next page).
H NEAR
(Hysteresis Near):
The output will ac vate un l the reading is greater than the Trip Reading + Trip Window,
at which point the output will deac vate and remain in that state un l the reading is less
than the Trip Reading (refer to chart on next page).
FAR
:
The output will ac vate whenever the reading is greater than the Trip Reading (refer to
chart on next page).
INCLSV
(Inclusive):
The output will ac vate whenever the reading is greater than the Trip Reading and less
than the Trip Reading + Trip Window (refer to chart on next page).
H FAR
(Hysteresis Far):
The output will ac vate when the reading increases beyond the Trip Reading + Trip
Window, and will remain ac ve un l the reading falls below the Trip Reading. The
output will remain deac vated un l the reading is once again greater than the Trip
Reading + Trip Window (refer to chart on next page).
ON
:
Holds the output closed whenever the display is powered.
OFF
:
Disables the output.