Introduction

8

Installation Environment Requirements

The Echo ACP is designed for use in a Unison DRd enclosure. The environmental

conditions for the Echo ACP should adhere to the requirements set for the DRd enclosure.

Reference the Unison DRd Rack Enclosure Installation Manual for complete details.

A clean (not dusty) temperature-controlled environment with an ambient temperature
of 32-104°F / 0-40°C and ambient humidity of 10-90%, non-condensing.

Restricted public access to prevent tampering.

Soundproofing or performance area separation to muffle ventilation fan noise is
recommended.

All CE equipment is tested to EMC category B environment.

Installation of the Echo ACP is as simple as sliding the module into the bottom guided slots

of the enclosure.

See “Install the Echo ACP” on page 15.

There are no wire terminations

made directly to the Echo ACP, instead all wire terminations are made to the host DRd

enclosure left and right I/O boards. Reference the Unison DRd Rack Enclosure Installation

Manual for complete wire termination details.

Compliance

UL and cUL Listed

CE Compliant

C A U T I O N :

HVAC systems must at all times maintain the specified ambient temperature at the

rack. Dimming systems operating within 10°F (5°C) of the upper or lower

temperature limits must strictly follow installation and operation guidelines to

operate reliably.