69

Echo ACP Configuration Manual

2 and 3 Wire Fluorescent Mode

Property

Units

Default 120V

Default 230V

Default 277V

Curve

not applicable Linear

Linear

Linear

Voltage Regulation

On / Off

On

On

On

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

56V

108V

130V

Max Scale

Volts

120V

230V

277V

Transformer Mode

On / Off

On

On

On

Threshold

Control

1% (>0%)

1% (>0%)

1% (>0%)

4 Wire Fluorescent Mode

Property

Units

Default 120V

Default 230V

Default 277V

Curve

not applicable Linear

Linear

Linear

Voltage Regulation

On / Off

Off

Off

Off

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

120 =Max

230 =Max

277 =Max

Max Scale

Volts

120

230

277

Transformer Mode

On / Off

On

On

On

Threshold

Control

1% (>0%)

1% (>0%)

1% (>0%)

Always On Mode

Property

Units

Default 120V

Default 230V

Default 277V

Curve

not applicable Linear

Linear

Linear

Voltage Regulation

On / Off

Off

Off

Off

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

0

0

0

Max Scale

Volts

120

230

277

Transformer Mode

On / Off

Off

Off

Off

Threshold

Control

0

0

0

DALI Mode

Property

Units

Default 120V

Default 230V

Default 277V

Curve

not applicable Linear

Linear

Linear

Voltage Regulation

On / Off

Off

Off

Off

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

0

0

0

Max Scale

Volts

120

230

277

Transformer Mode

On / Off

On

On

On

Threshold

Control

0

0

0

Advertising