Echo ACP Basic Navigation

22

Status / Errors Messages Generated by the DRd Dimming Engine

Message Displayed

Description

Action

Rack Error / Rack
Overtemp

Ambient temperature is
above rated temperature
range.

All dimmers in the enclosure are disabled
from use until the ambient temperature is
within an acceptable operating range.

Rack Warning / High
Operating Temp

Ambient temperature is
approaching maximum
temperature.

Correct the ambient temperature to within
specification.

Rack Warning / Low
Operating Temp

Ambient temperature is
below rated temperature
range.

Correct the ambient temperature to within
specification.

Rack Error/Freq out of
Range

Input power frequency is
out of operating range.

All dimmers in the enclosure are disabled
from use until the input power frequency is
within acceptable operating range.

Dimmer Overtemp/
Dimmers ## and ##

Dimmer is in an overtemp
condition.

The specified dimmer automatically
disables. Verify loads are within
acceptable limits. Try swapping dimmer
modules to isolate if the problem is within
a module.

Rack Error/Phase 1
Missing

Phase A is off.

Check mains power feed.

Rack Error/Phase 2
Missing

Phase B is off.

Check mains power feed.

Rack Error/Phase 3
Missing

Phase C is off.

Check mains power feed.

Rack Error/Phase 1
Overvoltage

Phase A voltage is above
rated voltage range.

All dimmers in the enclosure are disabled
from use until Phase A voltage is within
acceptable operating range.

Rack Error/Phase 2
Overvoltage

Phase B voltage is above
rated voltage range.

All dimmers in the enclosure are disabled
from use until Phase B voltage is within
acceptable operating range.

Rack Error/Phase 3
Overvoltage

Phase C voltage is above
rated voltage range.

All dimmers in the enclosure are disabled
from use until Phase C voltage is within
acceptable operating range

Rack Error/Phase 1
Undervoltage

Phase A voltage is below
rated voltage range.

Correct input voltage to acceptable range.

Rack Error/Phase 2
Undervoltage

Phase B voltage is below
rated voltage range.

Correct input voltage to acceptable range.

Rack Error/Phase 3
Undervoltage

Phase C voltage is below
rated voltage range.

Correct input voltage to acceptable range.

Rack Error/Fan Error or
Failure

Fan is not operating
properly.

Verify that the fan is not obstructed.