31

Echo ACP Configuration Manual

A universe is a group of 512 contiguous addresses. When using the “Patch sACN Input”

menu, addresses may start at one or any number up to 512 minus the number of dimmers

in the enclosure, depending on the type of enclosure(s) you are programming.

Patch sACN Input

You may use “and thru” functions to specify a selection or range of dimmers for sACN patch

editing. Once your selection is made, press enter (

) to accept the selection and begin

editing. To remove the last selected dimmer from the selection, press the back button ( ).

Continue pressing the back button ( ) to clear all undesired dimmers from the selection.

Step 1:

Make a selection of dimmers for sACN input patch using either the touch wheel
or the numeric button pad. Press enter (

) to accept the selection.

Step 2:

Assign a sACN input address to the first dimmer in the selection using the scroll
wheel or the numeric keypad, the press enter (

). The focus changes to the

Universe number.

If the selected dimmer is in dimmer doubled mode, the focus changes to the

second address (b) side of the dimmer.

a: As needed, assign a sACN input address to the second address (b) of the

dimmer doubled dimmer in the list and press enter (

) to accept the

selection. The focus changes to the Universe number.

Step 3:

Use the scroll wheel to select among the sACN Universes that have been

configured for this Echo ACP (refer to

Network Settings, page 41

).

Emergency Setup

The DRd enclosure detects a contact input and immediately triggers the panic/emergency

preset prior to processing any control levels, regardless of the condition of the enclosure

(physical, configuration, or firmware).

Emergency operation uses the emergency settings that are provided by the dimming

engine, as set in Emergency Setup menu, even if the Echo ACP configuration and the

dimming engine configuration do not match.

When panic is triggered in a DRd enclosure, the following menus are not accessible for

view or edit:

“Dimming Setup” menu

“Restore Defaults”, “Load Dimming Config”, and “Update Firmware” menus as found in
the “File Operations” menu.

The [recent] commands shortcut button

Emergency Dimmers

From the Emergency Setup menu, scroll to “Emergency Dimmers” and press enter (

).

Emergency Dimmers

Emergency Level:

100

Load Shedding:

On

Input Type:

Maintained

Active When:

Closed

Emergency Setup

The “Emergency Setup” provides access to the setup and

operation of dimmers when the integrated emergency bypass

operation is triggered. This operation is UL 924 Listed.