Install the echo acp, N o t e – ETC Echo Architectural Control Processor (ACP) v1.0.0 User Manual

Page 20

Advertising
background image

15

Echo ACP Configuration Manuall

Install the Echo ACP

The Echo ACP is designed to slide in the bottom module slot of a Unison DRd enclosure.

All data terminations used with the Echo ACP are terminated to the left and right I/O boards

in the DRd enclosure.

Install the Echo ACP only after the DRd enclosure has been installed and all wires have

been terminated properly.

Step 1:

Open the enclosure door.

Step 2:

Rest the Echo ACP on the bottom lip of the enclosure, aligning both left and right

edges with the module slots.

W A R N I N G :

Rack enclosures installed without an accessible power disconnect device

cannot be serviced or operated safely. Follow all local codes and

restrictions. Before installing or removing dimmer or control modules for

service, de-energize main feed to the rack and follow appropriate Lockout/

Tagout procedures as described in NFPA Standard 70E. It is important to

note that electrical equipment such as dimmer racks can present an arc

flash safety hazard if improperly serviced. This is due to available large

Short Circuit Currents on the feeders of the equipment. Any work on

energized equipment must comply with OSHA Electrical Safe Working

Practices.

N o t e :

DRd enclosures are shipped standard with a module retention bar which secures

all dimmer and control modules into the enclosure, requiring a tool for module

removal.
Before installing the Echo ACP module or any other modules, be sure to release

the retention bar first, install the modules, then reengage and secure the retention

bar.

W A R N I N G :

Never power up or operate the Unison DRd enclosure without all modules

installed. Failure to comply exposes you to dangerously high voltages that

may result in death by electrical shock.

Step 3:

Slide the Echo ACP into the rack.

Step 4:

Press gently on each corner of the

processor to ensure proper

connection with the card edge

connectors on the left and right I/O

boards.

Step 5:

Install the remaining dimmer

modules into their corresponding

module slots.

Step 6:

Slide the module retention bar to

the right and tighten the screws to

secure it in place.

Step 7:

Close the DRd enclosure door and

follow the final installation and

power up procedures defined in the

DRd Enclosure Installation Manual.

When power is applied, the status

LEDs will illuminate and the ACP

will load the operating software.