Dimmer modes, N o t e – ETC Echo Architectural Control Processor (ACP) v1.0.0 User Manual

Page 73

Advertising
background image

A

Dimmer Specifications

68

Dimmer Modes

Normal Mode

Property

Units

Default 120V

Default

230/240V

Default 277V

Curve

not applicable Mod-Square

Mod-Square

Mod-Square

Voltage Regulation

On / Off

On

On

On

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

6V

12V

14V

Max Scale

Volts

118V

230V

277V

Transformer Mode

On/Off

Off

Off

Off

Threshold

% Control

1% (>0%)

1% (>0%)

1% (>0%)

“Normal Mode” typically applies to standard dimmer modules.

Dimmer Doubled Mode

Property

Units

Default 120V

Default

230/240V

Default 277V

Curve

NA

Mod-Square

not applicable not applicable

Voltage Regulation

On / Off

On

not applicable not applicable

Dynamic Preheat

Seconds / Off

Off

not applicable not applicable

Min Scale

Volts

6V

not applicable not applicable

Max Scale

Volts

110V

not applicable not applicable

Transformer Mode

On / Off

not applicable not applicable not applicable

Threshold

% Control

1% (>0%)

not applicable not applicable

“Dimmer Doubled Mode” applies only to channels using ETC’s Dimmer Doubling™ technology.

N o t e :

“Dimmer Doubled Mode” does not apply to the DRd12-48 rack or any DRd rack

with an operating voltage of 230, 240, or 277V AC.

Switched Mode

Property

Units

Default 120V

Default 230V

Default 277V

Curve

not applicable Linear

Linear

Linear

Voltage Regulation

On / Off

Off

Off

Off

Dynamic Preheat

Seconds / Off

Off

Off

Off

Min Scale

Volts

0

12

14

Max Scale

Volts

120

230

277

Transformer Mode

On / Off

On

On

On

Threshold

Control

50

50

50

“Switched Mode” is typically the mode of operation for relay modules.

Advertising