Arch control status display – ETC Echo Architectural Control Processor (ACP) v1.0.0 User Manual

Page 25

Advertising
background image

2

Echo ACP Basic Navigation

20

internal operating temperature - The internal operating temperature is measured and
displays on the dimming rack status display. By default, temperature is displayed in °F
when the rack is 120, 240, or 277V AC, and in °C when the rack is 230 V AC.

rack software version - The rack software is specific to the dimming engine and may
differ from the ACP software version.

Arch Control Status Display

display title - A menu’s title appears in the first row of every display for easy navigation.

scroll to previous display - When the counter-clockwise symbol appears in the
display use the touch wheel to scroll counter-clockwise for the Dimming Rack Status
display. When the counter-clockwise symbol appears, use the touch wheel to scroll
counter-clockwise for the previous display.

Preset status - The second row of information displays presets status, for presets that
are configured and controlled by the host Echo ACP.

Sequence status and IP Address - The third row of data cycles between displaying
the Echo ACP IP address and the status of built-in sequences. The processor IP
address is set to Automatic IP address by factory default, and is only displayed if an
active Ethernet interface is detected.

System Message and Error Display - System messages are common to both the
dimming rack and ACP status displays. When a system error is detected, the message
changes to reflect the specific error type. When multiple errors are detected, each error
message cycles on the display, first by severity and then by chronological occurrence.
Reference

Status / Error Messages

for a complete listing of possible errors and the

actions required to clear them.

DMX Start: Indicates the DMX start address of the first circuit in the DRd enclosure. An
equal sign (=) before the address number indicates a 1 to 1 patch of DMX address to
the dimmers in the rack. An approximate equal sign

before the address number

indicates advanced patching. The DMX value is appended with (bal) when the rack is
configured for 3 phase or 1/bi-phase balanced. Reference the

Dimming Setup Menu,

page 27

for details on patching.

DMX Input and sACN Input: Cycles between the active status of the DMX input and
the sACN input, when configured.

Rack type and E-ACP software version - Displays the host rack type, manually set
or automatically detected and the installed version of Echo ACP software.

Arch Control Status

Preset 15 Active

Sequence Inactive

System OK

DMX Start = 155

DMX Input: Active

DRd12

v1.2.3

Advertising