Emergency level, N o t e – ETC Echo Architectural Control Processor (ACP) v1.0.0 User Manual

Page 37

Advertising
background image

3

Programming

32

“Emergency Dimmers” displays for dimmer assignment.

Settings include:

“On” which is the default and indicates the dimmer will turn on to the emergency preset
level when the emergency input is active.

“– –” indicated the dimmer is not in the emergency preset or is “Off”.

“NA” indicates a dimmer that is not applicable such as the CC20 or the second dimmer
for a single density module.

Step 1:

Use the touch wheel or the numeric button pad to select dimmers. You may also

use “and/thru” to specify specific or a range of dimmers. When the dimmer

selection, as seen in the title bar, is longer than the allowed 21 characters, an
ellipsis “...” will display at the beginning of the title bar. Press enter (

) to accept

the selection. The focus changes to the emergency value field.

Step 2:

Use the touch wheel to set the dimmer to either “On” or “– –”. Press enter (

)

to accept the selection.

Step 3:

Continue until all dimmers are set to the desired value.

Step 4:

Press the back button ( ) to return to the Emergency Setup menu.

Emergency Level

The Emergency level is the value that the emergency circuits will activate to when the

emergency panic input is active. The emergency level defaults to 100% but can be set to a

minimum setting of 80%.

Step 1:

Within the Emergency Setup menu, use the touch wheel to scroll to “Emergency
Level” and press enter (

).

Step 2:

Use the touch wheel or numeric button pad to change the emergency level to any
value between 0% and 100%. Press enter (

) to accept the selection.

N o t e :

Modules with single density or no density, such as the D20F or CC20 modules, do

not allow edits to the second dimmer position. The second dimmer position

defaults to “NA”.
For example, if the first dimmer in the rack (slot #1) is a D20F, a single density

fluorescent dimmer module, you would notice that dimmer number 1 could be set

to be “On” or “Off” depending on your operation requirements. Dimmer number 2

would be automatically set to “NA”. In this example, setting dimmer 1 to “On” will

include both the switched and the dimmed outputs in the emergency preset.

N o t e :

Dimmer doubled dimmers are shown with both “A” and “B” dimmers. When you

have selected the dimmer number, the “A” dimmer will be selected only by default.

Use the touch wheel to scroll and select the “B” side of the dimmer.

Emergency Dimmers

1:

O n

2: O n

3: --

4: O n

5: --

6: --

7: O n

8: O n

9: O n

1 0: --

11: O n

12: O n

13: N A

14: N A 15 A : O n

15 B:O n 16 A :O n 16 B:

O n

Assign dimmers to be “On” when the panic input is active and

assign other dimmers to turn off (also known as load-shedding).