AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Operation in advanced display mod

9.9.7.2

CONTROL RUN (start or stop the control program)

Main menu || SETUP || AS-I CONTROL || CONTROL RUN ||

This function is used to start or stop the control program. It modifies the START
BIT in the Control Info menu.

9.9.7.3

CONTROL FLAGS (control program flag memory)

Main menu || SETUP || AS-I CONTROL || CONTROL FLAGS ||

This function is used to read and modify the control program's flag memory.

First, a row needs to be selected using the soft keys.

Pressing OK displays the selected row.

After pressing OK, the display mode changes and it is now possible to select indi-
vidual flags using the soft keys. The selected flag is then displayed in binary for-
mat at the top row.

Pressing OK again enables editing the selected binary value.

CONTROL RUN
RUN
CHANGE

RUN: The control program has been started. The control program

can be stopped even if the start bit is set, for example if a con-
figuration error occurred or if the master is in configuration
mode.

STOP: The control program has been stopped.

CHANGE: Change the state between RUN and and STOP.

CONTROL FLAGS
0:2A 47 2B 2C
4:83 BD F2 58
...
124: 4A C3 84 7A

5:10111101

4:83 [BD] F2 58