Ec-flags and as-i detector – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 126

Advertising
background image

126

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

PROFIBUS DP

A rising edge of F2 and F3 switches the master to the desired mode.

A falling edge initiates deleting all bits in the LOS.

11.1.3.2

EC-Flags and AS-i detector

In addition to EC-flags, the AS-i detector flags are transferred with the AS-i diag-
nostic data.

Diagnostics data is designed as follows:

21

Slave 10B

Slave 11B

22

Slave 12B

Slave 13B

23

Slave 14B

Slave 15B

24

Slave 16B

Slave 17B

25

Slave 18B

Slave 19B

26

Slave 20B

Slave 21B

27

Slave 22B

Slave 23B

28

Slave 24B

Slave 25B

29

Slave 26B

Slave 27B

30

Slave 28B

Slave 29B

31

Slave 30B

Slave 31B

Byte

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

Flags

Input data

Output data

F0

ConfigError

Offline

F1

APF

LOS master bit

F2

peripheral fault

→ configuration mode

F3

ConfigurationActive

→ protected operating mode

Tab. 11-19.

ConfigError: 0 = config ok

1 = config error

APF: 0 = AS-i power ok

1 = AS-i power fail

peripheral fault: 0 = periphery ok

1 = peripheral fault

ConfigurationActive: 0 = protected mode

1 = configuration mode

Offline: 0 = online

1 = offline

LOS-Master-Bit 0 = offline by config error deactivated

1 = offline by config error activated