3 data sheet 103374, Data sheet 103374 – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 22

Advertising
background image

22

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Spezifications

4.1.3

Data sheet 103374

103374

PROFIBUS interface

according to DIN 19 245, part 3

Baud rates

9,6 kBaud up to 12000 kBaud, automatic recognition

DP functions

imaging of the AS-i slaves as I/O data of the PROFIBUS
complete diagnosis and configuration via the PROFIBUS DP

Serial interface

RS 232

AS-i cycle time

150

Ps

*

(number of slaves + 2)

Safety monitor

Release circuit

4-channel

Start delay

< 10 s

Respond delay

< 40 ms

Inputs:
4 x EDM/Start

EDM: inputs of external device monitoring circuits
Start: Start inputs
switching current statical 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs)

Outputs:
4 x output switching elements

relay outputs (output circuits 1 and 2)
max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V

semiconductor outputs (output circuits 3 and 4)
max. contact load: 0,5 A DC-13 at 30 V

Card slot

chip card for storage of configuration data

Displays

LCD

indication of slave adresses and error messages

LED power

power on

LED PROFIBUS

PROFIBUS master recognized

LED config error

configuration error

LED U AS-i

AS-i voltage OK

LED AS-i active

AS-i normal operation active

LED prg enable

automatic addresses programming enabled

LED prj mode

configuration mode active

LED AUX

auxiliary power

4 x LED EDM/Start

state of input of ext. device monitoring circuit
LED off:

open

LED on:

closed

Advertising