4 safety control/status, Command interface, Safety control/status – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 128

Advertising
background image

128

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

PROFIBUS DP

11.1.3.4

Command interface

11.1.4

Safety Control/Status

In the PROFIBUS configuration the designator Safety Control/Status can be add-
ed as cyclical data. This is possible both for the integrated Safety Monitor and for
2nd generation Monitors.

The state of the outputs and the message outputs is then inserted as a cyclical in-
put datum..

The cyclical output identifier contains the 4 Safety Monitor bits 1.Y1, 1.Y2, 2.Y1
and 2.Y2. The monitoring element “Monitor input” and the start elements “Monitor
Start-Monitor Input” and “Activation using Monitor Input” access these data. In
contrast, the “Feedback circuit” element always accesses the EDM input.

Information!

The description of the ASIMON program can be found in the separate software manual
„AS-i 3.0 Command interface“.

Information!

Generation III external Monitors allow a maximum of eight OSSDs to be sent.

Inputs

byte

description

1

Status OSSD 1, color-coded as defined in the table <Coding of status bytes>.

2

Status OSSD 2, color-coded as defined in the table <Coding of status bytes>.

Coding of status bytes

Bit [0 ... 3]

State or. color

0

green permanent lighting

1

green flashing

2

yellow permanent lighting

3

yellow flashing

4

red permanent lighting

5

red flashing

6

grey or off

7

reserved

Bit [6]

status or color

0

no device flashing yellow

1

at least one device flashing yellow

Bit [7]

status or color

0

no device flashing red

1

at least one device flashing red