2 earth/ground fault detector, 3 noise detector, 4 over-voltage detector – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 118: Earth/ground fault detector, Noise detector, Over-voltage detector

Advertising
background image

118

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Advanced Diagnostics for AS-i Masters

10.4.2

Earth/Ground Fault Detector

An Earth/Ground Fault exists when the voltage

U

GND

(Nominal value of

U

GND

=0,5 U

AS-i

.) is outside of the following range:

10% U

AS-i

≤ U

GND

≤ 90% U

AS-i

This error substantially limits the noise immunity of the AS-i communication.

Ground faults are indicated on the master´s display as well as in AS-i Control
Tools.

10.4.3

Noise Detector

The noise detector detects AC voltages on AS-i, that are not initiated by an AS-i
master or AS-i slaves. These interference voltages can cause telegram distur-
bances.

A frequent cause are insufficiently shielded frequency inverters or improperly
routed cables.

Noises is indicated on the master´s display as well as in AS-i Control Tools.

10.4.4

Over-voltage Detector

Over-voltages are present if the conductors of an AS-i network that normally are
routed electrically symmetrical with respect to machine ground, are strongly elec-
trically raised. A cause can for example be startup procedures of large consum-
ers.

However, over-voltages do generally not interfere with the AS-i communication,
but can under certain circumstances cause incorrect sensor signals.

Over-voltages are indicated on the master´s display as well as in the AS-i Control
Tools.

Information!

A ground fault in one of the two networks of a double master in a version 1 power sup-
ply for two AS-i networks causes a ground fault in the other network as well because of
the the existing galvanic connection.

Information!

To recognize ground faults the master must be grounded with its machine ground con-
nection.

Advertising