7 release circuits, 1 wiring overview of safety monitor, Release circuits – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 48: Wiring overview of safety monitor, 0 v, 24 v, For edm/start)

Advertising
background image

48

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Electrical connection

7.7

Release circuits

7.7.1

Wiring overview of safety monitor

1.Y1

Aux

2.Y1

K1

K3

1.Y2

2.Y2

K2

K4

2.13

+

24 V

2.Y1

0 V

+

1.13

2.Y2

1.Y2
2.14

+

4.14

+

1.14

1.Y1
3.14

1.Y1 (EDM 1/Start 1), 2.Y1 (EDM 2/Start 2), 1.Y2 (EDM 3/Start 3),
2.Y2 (EDM 4/Start 4)

The safety unit provides 4 inputs. The EDM & START inputs can be defined freely.
The inputs may not be connected to other potentials, but rather only directly or
through potential-free switches to + (for EDM/START).
Switching current static 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs).

3.14, 4.14

Semiconductor outputs. Max. contact load: 0.5 A DC-13 at 30 V.

1.14, 2.14; 1.13, 2.13

Potential-free relay contacts. Safety relay with one contact set for read-back. Max.
contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V.

0 V, 24 V

Semiconductor outputs are powered by separate 24 V DC.

+ (for EDM/Start)

Output supply, powered by AS-i. May not be connected to other potentials, but
rather only directly or through potential-free switches to one of the EDM or START
inputs. Voltage 30 ... 15 V

DC

.