EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 121

Advertising
background image

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

PROFIBUS DP

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

121

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

Safety Slaves B

Byte

description

1

0x0C header

2

0xAA (circuit 1)/0xAB (circuit 2) type

3

0x00 slot

4

0x00 spec

5

yellow flashing (0 ... 7)

6

yellow flashing (8 ... 15)

7

yellow flashing (16 ... 23)

8

yellow flashing (24 ... 31)

9

red flashing (0 ... 7)

10

red flashing (8 ... 15)

11

red flashing (16 ... 23)

12

red flashing (24 ... 31)

Tab. 11-9.

EC-Flags (high):

Bit 0: peripheral fault

Bit 1 … Bit 3: reserved

Bit 4: ground fault

Bit 5: over-voltage

Bit 6: noise

Bit 7: duplicate address

EC-Flags (low):

Bit 0: configuration error

Bit 1: slave with address 0 detected

Bit 2: Auto address assignment not available

Bit 3: Auto address assignment available

Bit 4: Configuration mode active

Bit 5: not in normal operation

Bit 6: AS-i power failure

Bit 7: AS-i master is offline

Delta list: List of AS-i slaves with configuration error.

1: ConfigError

0: no ConfigError

LPF: List of AS-i slaves with peripheral fault.

1: peripheral fault

0: no peripheral fault