12 analog outputs, Analog outputs, 6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 102

6 Configuration
102
6.12
Analog outputs
A maximum of three analog outputs can be configured as current or voltage outputs (standard
signal) and are freely scalable.
Setup dialog
Parameters
Parameter
Selection/settings
Description
Signal source
Analog selector (Inactive)
Analog signal that is issued via the ana-
log output.
If "Inactive" is selected, no signal is
issued.
Signal type
Physical output signal
0 ... 10 V
Standard signal for voltage
2 ... 10 V
Standard signal for voltage
0 ... 20 mA
Standard signal for current
4 ... 20 mA
Standard signal for current
Behavior on error Value of the output signal after deviation above or below the measuring range (out
of range = O-o-R)
The options "NAMUR Low" and "NAMUR High" are only available for signal types
2 ... 10 V and 4 ... 20 mA.
NAMUR Low
Value for deviation below measured
value/short-circuit according to NAMUR
recommendation
NAMUR High
Value for deviation above measured
value/probe break according to NAMUR
recommendation
Signal at O-o-R
Adjustable value (see "Signal at O-o-R"
parameter)
Last value
The last value is retained.
?