6 Configuration
96
6.11
Limit value monitoring
One of eight alarm functions can be selected for each of the four instances of limit value mon-
itoring in order to monitor a chosen input value (actual value) in relation to a fixed limit value or
a limit value relating to the setpoint value (setpoint value
limit value). Each instance of limit
value monitoring issues an output signal.
Setup dialog
Parameters
Parameter
Selection/settings
Description
Alarm function
Inactive
Limit value monitoring is inactive.
AF1
Limit value above and below the set-
point value (monitoring band around the
setpoint value)
AF2
As for AF1, output signal inverted
AF3
Limit value below the setpoint value
AF4
As for AF3, output signal inverted
AF5
Limit value above the setpoint value
AF6
As for AF5, output signal inverted
AF7
Fixed limit value
AF8
As for AF7, output signal inverted
Signal suppres-
sion
Digital selector (Inactive)
Signal (high-active) for suppressing the
output signal
Actual value
Analog selector (Inactive)
Analog signal as actual value (signal to
be monitored)
Setpoint value
Analog selector (Inactive)
Analog signal as setpoint value (refer-
ence signal for AF1 to AF6)
?