3 analog inputs, 4 electrical connection – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 33

33
4 Electrical connection
4.3.3
Analog inputs
Input 1, 2: Standard version; input 3, 4: Option
Connection
Input
Terminals
Symbol and terminal designation
Thermocouple
1
2
3
4
2 and 3
6 and 7
18 and 19
22 and 23
2, 6, 18, 22
3, 7, 19, 23
RTD temperature probe
2-wire circuit
1
2
3
4
2 and 4
6 and 8
18 and 20
22 and 24
2, 6, 18, 22
4, 8, 20, 24
RTD temperature probe
3-wire circuit
1
2
3
4
2 to 4
6 to 8
18 to 20
22 to 24
2, 6, 18, 22
3, 7, 19, 23
4, 8, 20, 24
RTD temperature probe
4-wire circuit
1
2
3
4
1 to 4
5 to 8
17 to 20
21 to 24
1, 5, 17, 21
2, 6, 18, 22
3, 7, 19, 23
4, 8, 20, 24
Voltage DC 0(2) to 10 V
1
2
3
4
1 and 2
5 and 6
17 and 18
21 and 22
1, 5, 17, 21
2, 6, 18, 22
Voltage DC 0 to 1 V
1
2
3
4
2 and 3
6 and 7
18 and 19
22 and 23
2, 6, 18, 22
3, 7, 19, 23
Current DC 0(4) to 20 mA,
Heater current AC 0 to 50 mA
1
2
3
4
3 and 4
7 and 8
19 and 20
23 and 24
3, 7, 19, 23
4, 8, 20, 24
Resistance transmitter
A = Start
E = End
S = Slider
1
2
3
4
2 to 4
6 to 8
18 to 20
22 to 24
2, 6, 18, 22
3, 7, 19, 23
4, 8, 20, 24
Resistance/potentiometer
2-wire circuit
1
2
3
4
2 and 4
6 and 8
18 and 20
22 and 24
2, 6, 18, 22
4, 8, 20, 24
U
+
-
x
U
+
-
x
I
+
-
x
E
S
A