6 digital outputs, 4 electrical connection – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 35

35
4 Electrical connection
4.3.6
Digital outputs
Standard version
In the standard version the controller module is equipped with relay or logic outputs (see “Order
details”).
The digital output numbering starts with 3. This allows the direct assignment to the LEDs of the
digital outputs (LED 3 to 10).
Optional
Connection
Output
Terminals
Symbol and terminal designation
Relay output (N/O)
3
4
12 and 13
15 and 16
12, 15
13, 16
Logic output DC 0/15 V
3
4
12 and 13
15 and 16
12, 15
13, 16
U
+
-
x
Connection
Output
Terminals
Symbol and terminal designation
Relay output (changeover
contact)
5
7
9
17 to 19
21 to 23
25 to 27
17, 21, 25
18, 22, 26
19, 23, 27
Relay output (N/O)
5
6
7
8
9
10
17 and 18
18 and 19
21 and 22
22 and 23
25 and 26
26 and 27
17, 21, 25
18, 22, 26
19, 23, 27
Solid-state relay
5
7
9
18 and 19
22 and 23
26 and 27
18, 22, 26
19, 23, 27
Open-collector output
C = Collector
E = Emitter
5
6
7
8
9
10
17 and 18
17 and 19
21 and 22
21 and 23
25 and 26
25 and 27
17, 21, 25
18, 22, 26
19, 23, 27
E
C
E
C