2 controller input, 6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 72

6 Configuration
72
6.9.2
Controller input
This menu is used to configure the input signals of the controller – incl. the signals for switching
off the controller and for parameter block changeover – and the parameters for manual mode.
Setup dialog
Parameters
Parameter
Selection/settings
Description
Actual value
Analog selector (Inactive)
Analog signal as process value
Filter time con-
stant
0 s to 0.6 s to 100 s
Time constant for adjusting the digital
input filter (0 s = filter off)
Parameter is only relevant for external
actual value (NV_...).
Decimal place x
Decimal places of actual value (x)
Auto
Automatic
XXXXX.
No decimal places
XXXX.X
One decimal place
XXX.XX
Two decimal places
XX.XXX
Three decimal places
X.XXXX
Four decimal places
Setpoint
Analog selector (Inactive)
Analog signal as controller setpoint
value
Decimal place w
Decimal places of setpoint value (w)
(Selection options as for Decimal place
x)
Outp. level feed-
back
Analog selector (Inactive)
Analog signal as output level feedback
?