6 Configuration
94
Signal source
Setup dialog
Parameters
Stop
If the ramp is stopped while a controller is in manual mode, the "manual mode active" digital
signal of the relevant controller channel must be selected (C01ManualMode to
C04ManualMode).
Start
The ramp can be started in synchronism with a digital signal. If no digital signal is selected, the
ramp starts upon entry of a new setpoint value, which then progresses with the specified ramp
slope.
Parameter
Selection/settings
Description
Starting value
Analog selector (Inactive)
Ramp start value is specified with ana-
log signal (e.g. current actual value of
relevant controller).
Abort
Digital selector (Inactive)
Signal (high-active) for aborting the
ramp (setpoint value adopts the value at
the start of the ramp).
Stop
Digital selector (Inactive)
Signal (high-active) for stopping the
ramp (setpoint value remains constant
at the current value).
Off
Digital selector (Inactive)
Signal (high-active) for switching off the
ramp function (setpoint value immedi-
ately assumes the specified end value).
Start
Digital selector (Inactive)
Signal (high-active) for starting the ramp
?
?