6 Configuration
104
6.13
Digital outputs
A maximum of eight digital outputs are available (output 3 to 10).
Setup dialog
Parameters
Contact type
This parameter can be used to invert the status. This function is available for all types of digital
output.
Status after change of configuration
Modified parameters are incorporated immediately.
Behavior after power on
During the initialization phase of the controller module, the output signal is inactive.
Parameter
Selection/settings
Description
Signal source
Digital selector (Inactive)
Signal that is issued via the digital out-
put.
Inactive = output inactive
Contact type
Switching behavior of digital output
Normally open contact (NO)
The output is active if the digital signal
(signal source) is active.
Normally closed contact (NC)
The output is inactive if the digital signal
(signal source) is active.
TAG number
7 characters
Identification marking (documentation in
PLC)
?
Type of digital output
"Active" status
"Inactive" status
Relay (N/O contact)
Closed
Open
Relay (changeover contact)
Operating position
Idle position
Logic output
High level (1)
Low level (0)
Solid state relay
Not inhibited
Inhibited
Open-collector output
Not inhibited
Inhibited