8 Configuration – in setup program only
8.1.1
Grid points
Customer-specific linearization is specified by entering up to 45 grid points (pairs of values X/
Y). Here, value X indicates the physical measured value (e.g. in mV, mA, or Ohm; depending
on the sensor type) and value Y indicates the linearized value (e.g. temperature in °C).
Setup dialog
Parameters
The domain of the linearization (measured values, x-axis) is checked in the module and limited
as follows:
Domain lower limit = Xmin - 0.0125 × (Xmax - Xmin)
Domain upper limit = Xmax + 0.03125 × (Xmax - Xmin)
Parameter
Selection/settings
Description
Measured value
(X)
-99999 to 0 to +99999
Value of the relevant grid point on the x-
axis
Linearized value
(Y)
-99999 to 0 to +99999
Value of the relevant grid point on the y-
axis
TIP!
A measured value beyond the domain limits causes an overange or an underrange (out-of-
range).