3 self-optimization, 6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 75

75
6 Configuration
6.9.3
Self-optimization
Self-optimization (SO) determines the optimum controller parameters for a PI or PID controller.
Setup dialog
Parameters
Parameter
Selection/settings
Description
Method
Oscillation
Oscillation method
Step response
Step response method
SO output 1, 2
Type of the first or second controller output
Switched
Relay output
Semiconductor
Solid state relay output, open-collector
output, or logic output
Continuous
Analog output
Standby outp.
level
-100 to 0 to +100
Output level at start of self-optimization
(for step response method)
Step size
10 to 30 to 100
Size of output level step (for step
response method)
Acceptance CY
Transfer of Cy cycle time after completion of self-optimization
No
No transfer
Yes
Transfer
Allow tune
Allow self-optimization generally
No
Self-optimization not permitted
Yes
Self-optimization permitted
?
?