6 Configuration

78

Optimization according to the step response method

Initially, a configurable standby output is produced until the actual value "settles" to a constant.
This is automatically followed by a configurable output level step (step size) to the control path.
Main applications of the step response method:
•

Optimization immediately after "power on" during startup (considerable time saving, stand-
by output setting = 0 %)

•

Control path does not oscillate easily (e.g. extremely well insulated furnace with low losses,
long oscillation period)

•

Actual value must not exceed the setpoint value
If the output level is known for the corrected setpoint value, overshooting is prevented with
the following setting:
Standby output + step size

 output level in corrected state

The progression of the output level and actual value depends of the status of the process at
the point when self-optimization starts:

Self-optimization during the startup
phase

Self-optimization during operation

t

y

S

y

t

x

w

t1 t2

t3

}

Dy

{

y

x

y

S

t1

t2

t3

Dy

t

t

w

y Output level

y Step size

y

S

Standby output

t1 Start of self-optimization

x Actual value

t2 Point of output level step

w Setpoint value

t3 End of self-optimization