6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 93

93
6 Configuration
Error processing
The ramp end value is specified by the active setpoint value (output signal of setpoint value
function). If this signal is "out of range", this affects the output signal of the ramp function. The
following circumstances may arise:
If the active setpoint value has returned to a valid value, the ramp function is continued with the
last ramp value that was valid before the error occurred.
If during such an error event, the ramp function is started, stopped, aborted, or switched off, a
differentiation must be made between the cases below:
Tolerance band monitoring is not active during an error event.
Active setpoint value (output signal of set-
point value function)
Output signal of ramp function
Underrange
Error value 1.0E+37
Overrange
Error value 2.0E+37
No value
Error value 3.0E+37
Valid value
Current ramp value
Action
Output signal of ramp function
Start
When the error event is over, the ramp function starts and the current ramp
value is issued.
Stop
This action is not possible in the event of an error.
Abort
When the error event is over, the ramp start value is issued.
Switch-off
When the error event is over, the ramp end value is issued.