2 bus cable specification, Bus cable specification, Baud rate / bus cable length – Lenze PROFIBU PC-based Automation User Manual

Page 21: Control technology | profibus communication manual

Advertising
background image

DMS 2.2 EN 07/2011 TD17

L

21

Control technology | PROFIBUS communication manual

Technical data

Bus cable specification

5.2

Bus cable specification

Please follow the specifications of the PROFIBUS user organisation for bus cables.

Baud rate / bus cable length
Adapt the baud rate to the length of the bus cable.

Field

Values

Cable resistance

135 ... 165 Ω/km, (f = 3 ... 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Twisted in pairs, insulated and shielded

Baud rate [kbps]

Max. bus length [m]

9.6 ... 93.75

1200

187.5

1000

500

200

1500

200

3000 ... 12000

100

Note!

The baud rate depending of the data volume, cycle time, and number of stations

should only be selected as high as required for the application.