2 bus cable specification, Bus cable specification, Baud rate / bus cable length – Lenze PROFIBU PC-based Automation User Manual
Page 21: Control technology | profibus communication manual
![background image](/manuals/565881/21/background.png)
DMS 2.2 EN 07/2011 TD17
L
21
Control technology | PROFIBUS communication manual
Technical data
Bus cable specification
5.2
Bus cable specification
Please follow the specifications of the PROFIBUS user organisation for bus cables.
Baud rate / bus cable length
Adapt the baud rate to the length of the bus cable.
Field
Values
Cable resistance
135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length
≤
30 nF/km
Loop resistance
< 110 Ω/km
Core diameter
> 0.64 mm
Core cross-section
> 0.34 mm
2
Cores
Twisted in pairs, insulated and shielded
Baud rate [kbps]
Max. bus length [m]
9.6 ... 93.75
1200
187.5
1000
500
200
1500
200
3000 ... 12000
100
Note!
The baud rate depending of the data volume, cycle time, and number of stations