Control technology | PROFIBUS communication manual

Commissioning of PROFIBUS

Detailed commissioning steps

6.2.6.2

Configuring the PROFIBUS master

How to configure the PROFIBUS master:

1. Add the bus interface to the PLC configuration:

The "ProfibusMaster" subelement represents the PROFIBUS interface of the IPC to

which the logic bus is connected.

2. Set DP parameters for the PROFIBUS master:

• The standard setting of the PROFIBUS master station address is ’1’. Only change

the setting if the address is to deviate from ’1’.

• The "highest station address" is incremented automatically with each added

slave. Thus the value should not be changed manually.

• The GSE file... button serves to open and inspect the device-related GSE file.
• The Groups... button leads to the Group properties dialog. The group properties

refer to the slaves assigned to the master.