Commissioning of PROFIBUS
Detailed commissioning steps
6.2.6.2
Configuring the PROFIBUS master
How to configure the PROFIBUS master:
1. Add the bus interface to the PLC configuration:
The "ProfibusMaster" subelement represents the PROFIBUS interface of the IPC to
which the logic bus is connected.
2. Set DP parameters for the PROFIBUS master:
• The standard setting of the PROFIBUS master station address is ’1’. Only change
the setting if the address is to deviate from ’1’.
• The "highest station address" is incremented automatically with each added
slave. Thus the value should not be changed manually.
• The GSE file... button serves to open and inspect the device-related GSE file.
• The Groups... button leads to the Group properties dialog. The group properties
refer to the slaves assigned to the master.