Control technology | PROFIBUS communication manual

Function libraries

BusDiag.lib function library

40

L

DMS 2.2 EN 07/2011 TD17

Inputs (VAR_INPUT)
The status is updated in the background. Thus, the input variables do not need to be pre-

assigned.

Outputs (VAR_OUTPUT)

Identifier/data type

Meaning/possible settings

ENABLE

BOOL

The function block is activated in an edge-controlled manner:

• Positive edge (TRUE) = diagnostics information is detected and READY is set to

TRUE.

DRIVERNAME

POINTER TO

STRING

Name of the driver (address of the name) to which the diagnostics order is to be

transmitted.

• If a ’0’ is entered here, the diagnostics order is passed to all available drivers.

DEVICENUMBER

INT

Identification of the bus which is managed by this module (driver).

• The instance results from the PLC configuration. The first node attached

corresponds to instance 0, the second one to the instance 1 and so on.

• For a second MC-PBM communication card, you must create a second

GetBusState instance with another %MByy address. In order to obtain the

extended diagnostics with the

DiagGetState function block ( 41)

, you must call

the block with Instance := 1.

Identifier/data type

Meaning/possible settings

READY

BOOL

Always TRUE: Processing of the diagnostics order is completed.

STATE

INT

When READY = TRUE, STATE indicates the current status of the block by one of the

following values. These values are assigned to global constants. The constants are

stored in the BusDiag.lib function library.

Value = 1 The bus is ok, no error.

• Constant BUSSTATE_BUSOK

Value = 2 A bus error has occurred.

• Constant BUSSTATE_BUSFAULT

Value = 3 There is no PROFIBUS communication or communication has been

aborted.

• Constant BUSSTATE_BUSNOTCOMMUNICATING

Value = 4 The PROFIBUS is set to STOPPED.

• Constant BUSSTATE_BUSSTOPPED

EXTENDEDINFO

ARRAY [0...129]

OF BYTE

1:1 relation between the ARRAY index and the station number of the slave.

Only the first three bits of the byte are used:

Bit 0 The PROFIBUS station is configured.
Bit 1 The PROFIBUS station is active at the bus.
Bit 2 The PROFIBUS station sends an error message.

• Detailed information can be obtained via the

DiagGetState

function block ( 41)

.

Note!

After the bus is activated, the slaves set the Error-Flag (bit 2) so that the master

first reads out the diagnostics information. If the diagnostics information for the

corresponding slave is read out via the

DiagGetState function block

( 41)

, the

Error-Flag is reset.