Control technology | PROFIBUS communication manual
Commissioning of PROFIBUS
Detailed commissioning steps
3. Go to the Bus parameters tab to set the baud rate for PROFIBUS:
4. Go to the Module parameters tab to set the "Byteorder wordmodules motorola"
parameter:
The "Byteorder wordmodules motorola" parameter determines how the data are
copied from PROFIBUS to the process image.
Setting
Description
No
Standard setting:
The data are received by the bus in Motorola format (Big Endian) and copied into the Intel format
(Little Endian). The user sees a correct integer value (INT) (example: ’0x1234’ ’0x1234’).
We recommend to keep this setting. Like this, the slave data are correctly transferred to the
process image.
Yes
The data are copied without being transposed from the bus to the process image. The user sees
a transposed integer value (INT) (example: ’0x1234’ ’0x3412’).
• Compatibility with other projects from the version 1.5