Control technology | PROFIBUS communication manual

Commissioning of PROFIBUS

Detailed commissioning steps

36

L

DMS 2.2 EN 07/2011 TD17

6.2.6.4

Compiling project data
To compile the project data, select the ProjectBuild menu command or press the <F11>

function key.

 If errors occurred during the compilation process, you can locate and eliminate them by

means of the »PLC Designer« error messages. Then compile the project data again.

 If no errors occurred during the compilation process, save the »PLC Designer« project to

the project folder.

6.2.6.5

Logging on to the control system with the »PLC Designer«
To log the »PLC Designer« on to the control system, select the menu command

OnlineLogin.

 For this, the PLC program must be error-free.
 Confirm the appearing query dialog whether the new program is to be loaded with Yes.

6.2.6.6

Loading and starting the PLC program

How to load and start the PLC program on the IPC:

1. Select the OnlineDownload menu command.
2. Select the required file in the appearing dialog window.
3. Confirm the selection by clicking the Open button.

• The file is loaded onto the IPC and saved there under the same name.
• The PROFIBUS is initialised.

4. Select the OnlineRun menu command.

• The PLC program is executed.
• The cyclic data transfer starts.

Tip!
The menu command OnlineRead file from PLC can be used to reload a file from

the IPC into the »PLC Designer« project.

Note!

• The bus starts even if not all stations at the bus are available.
• When the PLC program is stopped, (menu command OnlineStop) the cyclic

data transfer continues to run until a reset source is executed (Menu

command OnlineReset (original)).