10 dead-band (l_db), Dead−band (l_db), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual

Page 30: Analog signal processing, 10 dead−band (l_db)

Advertising
background image

2.2.10

Dead−band (L_DB)

Function library LenzeDrive.lib

Analog signal processing

2−20

L

LenzeDrive.lib EN 1.7

2.2.10

Dead−band (L_DB)

This FB eliminates disturbances around the zero point (e.g. interfering influences on analog input
voltages).

L_DB

nIn_a

±32767

nOut_a

nGain

nDeadBand

Fig. 2−19

Dead band (L_DB)

VariableName

DataType

SignalType

VariableType

Note

nIn_a

Integer

analog

VAR_INPUT

nOut_a

Integer

analog

VAR_OUTPUT

The signal is limited to ±32767.

nGain

Integer

VAR CONSTANT RETAIN

Gain

nDeadBand

Integer

VAR CONSTANT RETAIN

Dead band

Parameter codes of the instances

VariableName

L_DB1

SettingRange

Lenze

nGain

C0620

−10.00 ... 10.00

1.00

nDeadBand

C0621

0 ... 100.00 %

1.00

Function

n D e a d B a n d

n D e a d B a n d

n I n _ a

n O u t _ a

n O u t _ a

n I n _ a

n G a i n = 1 , 0 0

n D e a d B a n d = 6 , 1 0 % = 1 0 0 0

n G a i n = 2 , 0 0

n D e a d B a n d = 0 %

n G a i n

Fig. 2−20

Dead band and gain

·

In nDeadBand you can set the parameters for the dead band.

·

In nGain you can alter the gain.

·

100 % corresponds to 16384.