3 motor potentiometer (l_mpot), Motor potentiometer (l_mpot), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual

Page 80: Special functions, Parameter codes of the instances, Range of functions, Operation of the motor potentiometer, Initialization of the motor potentiometer

Advertising
background image

2.7.3

Motor potentiometer (L_MPOT)

Function library LenzeDrive.lib

Special functions

2−70

L

LenzeDrive.lib EN 1.7

2.7.3

Motor potentiometer (L_MPOT)

This FB replaces a hardware motor potentiometer. It is used as an alternative setpoint source that
is operated via two inputs.

L_MPOT

nOut_a

bUp_b

bDown_b

byInitFunction

byFunction

bInAct_b

dnActRetain

CTRL

nHighLimit

wTir

wTif

nLowLimit

dnActRetain

Fig. 2−69

Motor potentiometer (L_MPOT)

VariableName

DataType

SignalType

VariableType

Note

bUp_b

Bool

binary

VAR_INPUT

Motor potentiometer runs up to the upper limit.

bDown_b

Bool

binary

VAR_INPUT

Motor potentiometer runs down to the lower limit.

bInAct_b

Bool

binary

VAR_INPUT

Activates a function.

nOut_a

Integer

analog

VAR_OUTPUT

Setpoint output

dnActRetain

Double integer

VAR_IN_OUT

Stores the current setpoint.

nHighLimit

Integer

VAR CONSTANT RETAIN

Upper limit (16384

º 100% º C0011)

nLowLimit

Integer

VAR CONSTANT RETAIN

Lower limit (16384

º 100% º C0011)

wTir

Unsigned

Integer

VAR CONSTANT RETAIN

Acceleration time Tir (10

º 1 s)

wTif

Unsigned

Integer

VAR CONSTANT RETAIN

Deceleration time Tif (10

º 1 s)

byFunction

Byte

VAR CONSTANT RETAIN

Deactivation function

byInitFunction

Byte

VAR CONSTANT RETAIN

Initialization function

Parameter codes of the instances

VariableName

L_MPOT1

SettingRange

Lenze

nHighLimit

C0260

−199.99 ... 199.99%

100.00

nLowLimit

C0261

−199.99 ... 199.99%

−100.00

wTir

C0262

0.1 ... 6000.0 s

10.00

wTif

C0263

0.1 ... 6000.0 s

10.00

byFunction

C0264

0 ... 5

0

byInitFunction

C0265

0 ... 2

0

Range of functions

·

Operation of the motor potentiometer

·

Initialization of the motor potentiometer

·

Store the current output value after supply interruption.

Advertising